Single Core Cables, with stranded Circular Aluminum conductors, XLPE insulated, Aluminum wire armor and PVC Sheath. 12/20 (24)

  • Stranded circular compacted Aluminum conductor, Semi-conducting layer as conductor screen, XLPE insulated, semi-conducting layer as non-metallic insulation screen, copper tape or wire as a metallic screen, wrapped with binder tape, covered with a layer of PVC as bedding layer, Aluminum wire armored and PVC sheathed.

 

  • Cables are produced according to IEC 60502-2 or BS6622.

 

.

Summary of cables specifications
AT14X401X1 Single Core
Aluminum
XLPE
50 0.641 0.822 - - 163 162 136 189 193 - 30.5 1080 0.1812 - 0.4567 0.503 PVC
AWA
AT15X401X1 Single Core
Aluminum
XLPE
70 0.443 0.5682 - - 200 199 167 236 240 - 32.8 1280 0.2031 - 0.4356 0.4819 PVC
AWA
AT16X401X1 Single Core
Aluminum
XLPE
95 0.32 0.4106 - - 238 237 200 285 288 - 34.3 1415 0.2235 - 0.4161 0.4623 PVC
AWA
AT17X401X1 Single Core
Aluminum
XLPE
120 0.253 0.3248 - - 269 268 227 328 330 - 35.9 1565 0.2424 - 0.4019 0.4481 PVC
AWA
AT18X401X1 Single Core
Aluminum
XLPE
150 0.206 0.2646 - - 301 299 289 370 372 - 37.3 1710 0.2612 - 0.3886 0.4348 PVC
AWA
AT19X401X1 Single Core
Aluminum
XLPE
185 0.164 0.2109 - - 340 336 336 424 424 - 39 1885 0.2839 - 0.3721 0.4184 PVC
AWA
AT20X401X1 Single Core
Aluminum
XLPE
240 0.125 0.1612 - - 392 387 390 498 493 - 41.3 2145 0.3146 - 0.3564 0.4026 PVC
AWA
AT30X401X1 Single Core
Aluminum
XLPE
300 0.1 0.1294 - - 437 424 378 568 553 - 45.3 2630 0.3465 - 0.35 0.3962 PVC
AWA
8T40X401X1 Single Core
Aluminum
XLPE
400 0.0778 0.1014 - - 494 472 430 654 630 - 48.2 3035 0.3823 - 0.3363 0.3825 PVC
AWA
AT50X401X1 Single Core
Aluminum
XLPE
500 0.0605 0.0798 - - 557 523 488 752 711 - 52.3 3595 0.4286 - 0.326 0.3722 PVC
AWA
AT60X401X1 Single Core
Aluminum
XLPE
630 0.0469 0.0631 - - 623 574 552 859 800 - 56 4210 0.4749 - 0.3149 0.3611 PVC
AWA
AT70X401X1 Single Core
Aluminum
XLPE
800 0.0367 0.0509 - - 691 624 618 977 893 - 61 5030 0.5382 - 0.3023 0.3485 PVC
AWA

 

These cables are generally suitable for direct burial or for installation on trays or in ducts.

  • IEC 60502-2
  • BS 6622

Download the full specifications PDF for more info