Single Core Cables, with Stranded Circular Copper Conductors, XLPE Insulated and PVC Sheathed. 0.6/1 (1.2) kV

  • Soft annealed stranded copper conductor, insulated with an XLPE compound covered with a layer of PVC compound to form the overall jacket.
  • Cables are produced according to IEC 60502-1 and BS 7889.

.

Summary of cables specifications
CT10X101U2 Single Core
Copper
XLPE
10 1.83 - 2.33 107 94 74 92 87 75 8.3 150 PVC
Unarmored
CT11X101U2 Single Core
Copper
XLPE
16 1.15 - 1.47 126 121 95 128 121 105 9.3 210 PVC
Unarmored
CT12X101U2 Single Core
Copper
XLPE
25 0.727 - 0.927 164 155 120 157 151 133 11 315 PVC
Unarmored
CT13X101U2 Single Core
Copper
XLPE
35 0.524 - 0.669 195 187 149 197 190 167 12.1 410 PVC
Unarmored
CT14X101U2 Single Core
Copper
XLPE
50 0.387 - 0.494 229 218 178 243 231 202 13.8 555 PVC
Unarmored
CT15X101U2 Single Core
Copper
XLPE
70 0.268 - 0.343 287 269 218 306 295 260 15.7 760 PVC
Unarmored
CT16X101U2 Single Core
Copper
XLPE
95 0.193 - 0.248 338 320 264 382 370 318 17.7 1015 PVC
Unarmored
CT17X101U2 Single Core
Copper
XLPE
120 0.153 - 0.197 389 366 298 444 433 375 19.6 1280 PVC
Unarmored
CT18X101U2 Single Core
Copper
XLPE
150 0.124 - 0.16 429 407 338 503 491 42B 21.8 1570 PVC
Unarmored
CT19X101U2 Single Core
Copper
XLPE
185 0.0991 - 0.129 493 463 384 583 572 485 23.9 1920 PVC
Unarmored
CT20X101U2 Single Core
Copper
XLPE
240 0.0754 - 0.099 567 532 440 716 705 590 27.1 2530 PVC
Unarmored
CT30X101U2 Single Core
Copper
XLPE
300 0.0601 - 0.081 641 595 498 906 832 682 29.7 3105 PVC
Unarmored
CT40X101U2 Single Core
Copper
XLPE
400 0.047 - 0.0638 732 676 561 982 959 785 33.9 4135 PVC
Unarmored
CT50X101U2 Single Core
Copper
XLPE
500 0.0366 - 0.0517 829 755 623 1109 1086 895 37.4 5110 PVC
Unarmored
CT60X101U2 Single Core
Copper
XLPE
630 0.0283 - 0.0425 950 847 710 1271 1247 1052 41.9 6455 PVC
Unarmored
CT70X101U2 Single Core
Copper
XLPE
800 0.0221 - 0.0292 1043 938 801 1444 1421 1201 46.8 8260 PVC
Unarmored

Coming Soon

• For outdoor and indoor installations in damp and wet locations. They are normally used for power distribution in
urban networks, industrial plants, as well as in thermopower and hydropower stations.
  • IEC 60502-1
  • BS 7889

Download the full specifications PDF for more info
SPECS PDF